A_Better_Antenna_Balun_ZS1AN.pdf

(192 KB) Pobierz
A Better
Antenna-Tuner Balun
Which balun to use? The hybrid balun promises
advantages over both voltage and current baluns.
By Andrew Roos, ZS1AN
B aluns that are situated be-
is effective only if the load impedance
is well balanced with respect to
ground.
I then introduce a new design: the
“hybrid” balun, which overcomes these
limitations of the voltage and current
baluns. It can operate with much
higher load impedances than can cur-
rent baluns and with unbalanced load
impedances that voltage baluns could
not drive effectively. The article con-
cludes by describing a simple test I
conducted to confirm that the hybrid
balun operates as predicted.
Fig 1. Although Z W is shown on only
one of the transformer windings, its
effects are felt equally on both wind-
ings due to the coupling action of the
“ideal transformer,” which can be
expressed by two rules:
1. The currents in the two windings
of the “ideal transformer” are equal
and opposite.
2. V AC = V BD = ( I 1 I 2 ) Z W
The model assumes that the length
of the transmission line used to con-
struct the TLT is short in terms of
wavelength, so transmission line ef-
fects can be ignored. Although this as-
sumption holds for the lower part of
the HF region, some transmission-
line effects do come into play at higher
frequencies.
The use of this model does not im-
ply that TLTs operate like conven-
tional transformers. The ideal
tween an antenna tuning unit
and a non-resonant antenna
may be subjected to high-impedance,
highly reactive or unbalanced loads
that can prevent the balun from func-
tioning effectively.
In this article, I apply the analyti-
cal model of the transmission-line
transformer developed by Roy
Lewallen 1 to analyze the performance
of the 1:1 current balun and the 4:1
voltage balun in this application. The
analysis shows that the current balun
operates effectively only for small load
impedances, while the voltage balun
Lewallen’s Model of a 1:1 Trans-
mission-Line Transformer
Lewallen models the 1:1 transmis-
sion-line transformer (TLT) as an
ideal 1:1 transformer with a “wind-
ing impedance,” Z W , in parallel with
one of the windings, 2 as shown in
1 Notes appear on page 34.
PO Box 350, Newlands
7725, South Africa
zs1an@qsl.net
Sep/Oct 2005 29
1006811345.069.png 1006811345.080.png 1006811345.091.png
1:1 transformer is simply a modeling
convenience, and the resulting model
applies to any device that exhibits
common-mode impedance, irrespec-
tive of its operating principle.
I 2 = V S / Z 2
We can calculate Witt’s measure of
imbalance:
IMB = 2 | I 1 I 2 | / | I 1 + I 2 |
= 2 | Z 2 Z 1 | / | Z 2 + Z 1 |
The 4:1 Voltage Balun
We can use the same model to ana-
lyze the performance of the Ruthroff ’s
4:1 voltage balun shown in Fig 3. Once
again, Z 1 and Z 2 represent the load.
According to Lewallen’s model, the
voltages across the two windings of the
transmission-line transformer (TLT)
are equal, and both equal V S , so
I 1 = V S / Z 1
and
(Eq 4)
The 1:1 Current Balun
Fig 2 shows the schematic of
Guanella’s 1:1 “current” balun. Z 1 and
Z 2 represent the load. The junction
between Z 1 and Z 2 is grounded to rep-
resent the (typically capacitive) cou-
pling of the antenna system to ground.
The load is balanced with respect to
ground when Z 1 = Z 2 .
The principle limitation of this
balun is that it can only maintain bal-
ance between the currents flowing into
the load, I 1 and I 2 , for relatively low
load impedances. The ability to main-
tain the correct current balance in the
load is of course the reason for using
a balun in the first place, so the
extent to which a balun maintains this
balance is the primary measure of its
effectiveness. In the case of the 1:1 cur-
rent balun, Lewallen shows that
I 1 / I 2 = ( Z 2 + Z W ) / Z W (Eq 1)
Where Z W is the “winding imped-
ance” (common-mode impedance) of
the balun. We can use this to calcu-
late the measure of imbalance pro-
posed by Witt 3 as:
IMB = 2 |( I 1 I 2 ) / ( I 1 + I 2 )|
= 2 |( I 1 I 1 ( Z 2 + Z W )/ Z W ) / ( I 1 + I 1 ( Z 2
+ Z W )/ Z W )|
= 2 | Z 2 | / |( Z 2 + 2 Z W )| (Eq 2)
(Note that | X | means the magni-
tude of complex variable X .) If IMB is
small, then | Z W | >> Z 2 . So as a good
approximation,
IMB = | Z 2 | / | Z W | (Eq 3)
Although Witt does not suggest an
acceptable maximum figure for IMB,
0.1 seems a reasonable value since
this means that the magnitude of the
common-mode (unbalanced) current
flowing in the antenna is one-tenth the
magnitude of the differential-mode
(balanced) current. To prevent IMB
from exceeding 0.1 we require that
| Z 2 |
The degree to which the currents
are balanced depends only on the bal-
ance of the load impedances with re-
spect to ground. In order to keep
IMB
0.1, the impedances must be
I 1
C
A
I 1
I 2
B
D
Z W
I 1 -I 2
qx0509-roos01
Fig 1—Lewallen’s model of the 1:1 TLT.
I 1
V S
Z 1
Z 2
I 2
qx0509-roos02
Fig 2—A schematic of Guanella’s 1:1 current balun.
I 1
0.1 | Z W |. This limits the use-
fulness of the current balun. Charles
Rauch 4 measured the common-mode
impedance of several commercially
manufactured current baluns using a
network analyzer and found that most
had a common-mode impedance of less
than 1 k
Z 1
V S
V S
V S
Z 2
at 15 MHz, giving a maxi-
mum acceptable value of | Z 2 | of less
than 100
Ω
I 2
. For balanced loads, this
means that the baluns tested by
Rauch would be effective only for load
impedances under 200
Ω
qx0509-roos03
Fig 3—A schematic of Ruthroff’s 4:1 voltage balun.
Ω
.
30 Sep/Oct 2005
1006811345.102.png 1006811345.001.png 1006811345.012.png 1006811345.021.png 1006811345.022.png 1006811345.023.png 1006811345.024.png 1006811345.025.png 1006811345.026.png 1006811345.027.png 1006811345.028.png 1006811345.029.png 1006811345.030.png 1006811345.031.png 1006811345.032.png 1006811345.033.png 1006811345.034.png 1006811345.035.png 1006811345.036.png 1006811345.037.png 1006811345.038.png 1006811345.039.png 1006811345.040.png 1006811345.041.png 1006811345.042.png 1006811345.043.png 1006811345.044.png 1006811345.045.png 1006811345.046.png 1006811345.047.png
within about 10% of each other.
Imbalance does not impose any con-
straint on the maximum impedance
a voltage balun can drive. This is de-
termined by efficiency considerations
and is usually greater than the mag-
nitude of the winding inductance, so
the voltage balun can drive balanced
loads at least five times larger than
can a current balun with the same
winding impedance.
Unfortunately, supposedly
balanced antennas may present un-
balanced loads due to the presence
of nearby conductors or asymmetry
in the antenna installation imposed
by site constraints. Kevin Schmidt 5
describes one such case:
“One of my antennas is a ‘dipole’
about 60 feet on a leg running around
the outside of my 1-story house. It is fed
by about 30 feet of 300
through ferrite beads as suggested by
Walt Maxwell 8 for the choke, Rauch’s
measurements (see Note 4) show that
beaded coax chokes have a large re-
sistive component to their common-
mode impedance. Equation 13 shows
that this will increase the choke’s
power dissipation and reduce the ef-
ficiency of the balun. The voltage
balun found on many ATUs can be
converted to a hybrid balun by sim-
ply adding a common-mode choke
after the balun, without need for
modification to the ATU or balun.
Although the common-mode choke
appears identical to the 1:1 current
balun, the term “common-mode choke”
is preferred, as it is driven by the bal-
anced voltage at the output of the volt-
age balun, instead of having one side
grounded. This means the voltage
across the windings is no longer the
full source voltage V S , but only a por-
tion of V S that depends on the degree
of imbalance of the load. Consequently,
the common-mode choke does not suf-
fer from the limitation of the current
balun—that | Z 2 | must be less than
one tenth of | Z W | in order to main-
tain balance and can operate effec-
tively and efficiently at much higher
impedance levels than could a current
balun. In turn, the choke presents a
balanced load impedance to the volt-
age balun preceding it, despite any
imbalances in the antenna system,
allowing the hybrid balun to drive
unbalanced loads more effectively
than could the voltage balun alone.
Let V C be the common-mode volt-
age across the choke windings as
shown in Fig 5. Since V C also appears
across the winding impedance Z W in
Lewallen’s model, and the current
flowing through the winding imped-
ance is the common-mode current
I 1 I 2 ,
V C = ( I 1 I 2 ) Z W (Eq 5)
The voltages at the input side of the
choke are V S and – V S , so
I 1 = ( V S V C ) / Z 1
TV twinlead.
The legs of the ‘dipole’ are not straight,
and it isn’t symmetric about the feed
point, since the shack is at a corner of
the house.”
He measured the differential and
common-mode impedances of the an-
tenna at 3.52 MHz using professional
instruments and obtained the results
shown in Fig 4. 6 If this antenna were
driven by a voltage balun, IMB would
be 0.22. This shows that the inherent
balance of amateur antennas cannot
be assumed, so antenna tuner baluns
must be able to drive unbalanced loads
effectively.
Ω
(Eq 6)
and
I 2 = ( V S + V C ) / Z 2 (Eq 7)
Substituting Equations 6 and 7 into
Equation 5 and solving for V C ,
Z 1 = 191 + 358j
Z 2 = -33 + 176j
Fig 4—The
impedances of
Schmidt’s dipole.
The Hybrid Balun
The preceding sections have shown
that the current balun is limited by
its inability to maintain current bal-
ance when driving all but low-imped-
ance loads, while the voltage balun
cannot maintain current balance in
unbalanced loads. Since the mainte-
nance of current balance in the load
is the principle purpose of a balun,
these limitations warrant a search for
“a better balun.” This section de-
scribes and analyses the “hybrid
balun,” which consists of a voltage
balun followed by a common-mode
choke. The circuit shown in Fig 5 uses
a 4:1 voltage balun, but a 1:1 voltage
balun would work equally well and
the analysis is identical.
The hybrid balun requires two
separate transmission-line trans-
formers. The TLT for the voltage balun
is best realized using a bifilar wind-
ing on a toroidal ferrite or powdered-
iron core. The “hardy” balun designs
offered by Dr Sevick 7 would be
excellent in this application. I also rec-
ommend this approach for the com-
mon-mode choke. Although one could
use a length of coaxial cable threaded
Z 3 = 887 + 622j
qx0509-roos04
Voltage Balun
Common-Mode Choke
V C
I 1
Z 1
V S
V S
V C
V S
Z 2
I 2
qx0509-roos05
Fig 5—A schematic of the 4:1 hybrid balun.
Sep/Oct 2005 31
1006811345.048.png 1006811345.049.png 1006811345.050.png 1006811345.051.png 1006811345.052.png 1006811345.053.png 1006811345.054.png 1006811345.055.png 1006811345.056.png 1006811345.057.png 1006811345.058.png 1006811345.059.png 1006811345.060.png 1006811345.061.png 1006811345.062.png 1006811345.063.png 1006811345.064.png 1006811345.065.png 1006811345.066.png 1006811345.067.png
V C = V S Z W ( Z 2 Z 1 ) / ( Z 1 Z 2 + Z W Z 1 +
Z W Z 2 )
given in Eq 8 and canceling | V S | 2
gives
P C / P V = | Z W ( Z 2 Z 1 ) / ( Z 1 Z 2 + Z W Z 1
+ Z W Z 2 )| 2
maintain the current balance in the
load. If the load is perfectly bal-
anced, the choke dissipates no
power. In the worst case, when Z 1 or
Z 2 is zero (a completely unbalanced
load), IMB = 2, and the choke dissi-
pates the same power as the volt-
age balun. Such an extreme case is
unlikely, however, and under normal
conditions (with IMB < 1) the choke
dissipates less than one quarter of
the power dissipated by the voltage
balun, so the overall efficiency of the
hybrid balun is only slightly less
than that of a voltage balun driving
a balanced load (which, incidentally,
is the same as that of a current
balun driving a balanced load, since
in both cases the voltage across the
TLT windings is one half of the volt-
age across the load).
(Eq 8)
We can substitute this value into
equations 6 and 7 to obtain
I 1 = V S ( Z 2 + 2 Z W ) / ( Z 1 Z 2 + Z 1 Z W + Z 2
Z W )
(Eq 15)
When | Z W | is small compared to
| Z 1 Z 2 |, this approaches zero, so the
efficiency of the hybrid balun is the
same as that of the voltage balun.
When | Z W | is large compared to | Z 1
Z 2 |, it approaches
P C / P V = |( Z 2 Z 1 ) / ( Z 1 + Z 2 )| 2
(Eq 16)
Substituting the value of IMB for
the voltage balun given in Eq 4,
P C / P V = 1/4 IMB 2
(Eq 9)
and
I 2 = V S ( Z 1 + 2 Z W ) / ( Z 1 Z 2 + Z 1 Z W + Z 2
Z W )
(Eq 10)
So Witt’s measure of imbalance is
IMB = 2 |( I 1 I 2 ) / ( I 1 + I 2 )|
= 2 |( Z 2 Z 1 ) / ( Z 1 + Z 2 + 4 Z W )|
(Eq 11)
Comparing this to Eq 4, which
gives IMB for the voltage balun, we
see that the additional term in the
denominator reduces the imbalance
by a factor of
IMB V / IMB H = |1 + 4 Z W / ( Z 1 + Z 2 )|
(Eq 17)
So when | Z W | is large, the addi-
tional power lost in the common-
mode choke is proportional to the
square of the imbalance that would
have existed in the load if it was
driven by the voltage balun alone.
This suggests the interpretation
that the power dissipated by the
choke depends on the amount of
work the choke has to do in order to
Comparison of Balun
Performance
The chart in Fig 6 shows the regions
in which the different baluns will op-
erate effectively for purely resistive
loads. R 1 and R 2 , the resistive (real)
(Eq 12)
Where IMB V and IMB H are the im-
balance measures for the voltage
balun and the hybrid balun, respec-
tively, with the same loads.
1
Efficiency of the Hybrid Balun
Efficiency is as important as bal-
ance for antenna tuner baluns. The
power loss in a TLT can be derived
from Lewallen’s model by noting that
the power loss in each winding is the
dot product of the voltage across the
winding, V W , and the current flowing
in the winding, so the total power loss
in both windings is:
P LOSS = V W · I 1 + V W · (– I 2 )
= V W ( I 1 I 2 )
= V W ( V W / Z W )
= R e ( V W* ( V W / Z W )*)
= R e(| V W | 2 / Z W *)
= | V W | 2 R e( Z W ) / | Z W | 2 (Eq 13)
Where “ X *” means the complex con-
jugate of “ X ” and “Re( X )” means the
real component of “ X .” This interest-
ing result shows that the power dissi-
pation in the TLT is proportional to
the square of the voltage across the
TLT windings. So for the hybrid balun
(refer to Fig 5) if the winding imped-
ances of the two TLTs are the same,
the relationship between P C , the power
dissipated in the common-mode choke
and P V , the power dissipated in the
voltage balun is given by
P C / P V = | V C | 2 / | V S | 2
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
R1
Current (upper bound)
Voltage (lower bound)
Voltage (upper bound)
Hybrid (lower bound)
Hybrid (upper bound)
(Eq 14)
Substituting the formula for V C
Fig 6—Effective operating regions of the current, voltage and hybrid baluns.
32 Sep/Oct 2005
1006811345.068.png 1006811345.070.png 1006811345.071.png 1006811345.072.png 1006811345.073.png 1006811345.074.png 1006811345.075.png 1006811345.076.png 1006811345.077.png 1006811345.078.png 1006811345.079.png 1006811345.081.png 1006811345.082.png 1006811345.083.png 1006811345.084.png 1006811345.085.png 1006811345.086.png 1006811345.087.png 1006811345.088.png 1006811345.089.png 1006811345.090.png 1006811345.092.png 1006811345.093.png 1006811345.094.png 1006811345.095.png 1006811345.096.png 1006811345.097.png 1006811345.098.png 1006811345.099.png 1006811345.100.png 1006811345.101.png 1006811345.103.png 1006811345.104.png 1006811345.105.png 1006811345.106.png 1006811345.107.png 1006811345.108.png 1006811345.109.png 1006811345.110.png 1006811345.111.png 1006811345.112.png 1006811345.002.png 1006811345.003.png 1006811345.004.png 1006811345.005.png 1006811345.006.png
components of Z 1 and Z 2 , are shown
on the X and Y axes. The plot lines rep-
resent the upper and lower bounds of
the regions in which each of the baluns
will maintain a load imbalance (IMB)
not exceeding 0.1. The chart is normal-
ized for | Z W | = 1.
The horizontal line near the bottom
of the chart is the upper bound of the
current balun’s operating region,
showing that the current balun is ef-
fective when R 2 < 0.1 | Z W |, irrespec-
tive of the value of R 1 . (Although the
current balun is able to drive high-
impedance loads that are situated
near the X-axis, this not terribly use-
ful since the limiting case as R 2 / R 1
0 is an unbalanced load being driven
by an unbalanced source, so no balun
is required.) The two lines that meet
at the origin represent the upper and
lower bounds of the region in which
the voltage balun can maintain IMB
0.1. The voltage balun is effective for
much larger load impedances than the
current balun, but only when the load
is well balanced (a perfectly balanced
load would be situated on a 45° line
passing through the origin). The
angled lines that intersect the X and
Y axes at the value 0.2 are the lower
and upper bounds of the region in
which the hybrid balun is effective.
The hybrid balun is effective for higher
load impedances than the current
balun (excluding loads situated near
the X axis), and for a greater degree
of load asymmetry than the voltage
balun.
Although the chart displays only
purely resistive loads, similar results
are obtained for load impedances that
include both resistance and reactance.
Any load that has a small resistive
component combined with a large
reactive component, however, may
cause inefficiency and excessive heat-
ing in all balun types. If you have a
load like this, you need to transform
the load impedance, either by using a
balanced tuner or by adjusting the
length of the transmission line be-
tween the balun and the antenna.
Fig 7—The prototype hybrid balun.
5.0
4.0
3.0
2.0
Practical Testing
It would require more sophisticated
test equipment than I have to directly
measure the current balance achieved
by the different types of balun. Fortu-
nately, the input impedance of the volt-
age balun approximately equals the
value of Z 1 in parallel with Z 2 . This
provides a good indication of load-bal-
ance quality. That indication is the
extent to which the input impedance
of the balun approaches the value ex-
pected for a perfectly balanced load.
For the 4:1 balun, this is one quarter
1.0
0.0
0
20
40
60
80
100
120
140
160
180
200
R1 (ohms)
QX0509-Roos08
Voltage Balun
Hybrid Balun
Fig 8—SWR measured at the balun input for different ground-tap positions.
Sep/Oct 2005 33
1006811345.007.png 1006811345.008.png 1006811345.009.png 1006811345.010.png 1006811345.011.png 1006811345.013.png 1006811345.014.png 1006811345.015.png 1006811345.016.png 1006811345.017.png 1006811345.018.png 1006811345.019.png 1006811345.020.png
 
Zgłoś jeśli naruszono regulamin