5091-6310E.pdf

(945 KB) Pobierz
Effective Multi-tap
Transformer Measurement
using a Scanner and the
Agilent 4263B LCR Meter
Application Note 1224-5
935955107.024.png 935955107.025.png 935955107.026.png 935955107.027.png 935955107.001.png 935955107.002.png 935955107.003.png 935955107.004.png 935955107.005.png 935955107.006.png 935955107.007.png 935955107.008.png 935955107.009.png 935955107.010.png 935955107.011.png 935955107.012.png 935955107.013.png 935955107.014.png 935955107.015.png
 
Introduction
Agilent 4263B Transformer
Measurement Capability
With the progress of recent electronics equipment and
digital networks, production amounts are increasing
of the transformers which contribute to equipment
miniaturization, low power dissipation and higher quality.
Therefore, improvement of select estimate efficiency is
required at the production line or incoming inspection.
Noticed recently, improvement of estimation efficiency is
required for pulse transformers which are used in LAN
or ISDN digital networks, and for multi.-tap transformers
with three or more pole taps, such as switching power
transformers. This application note shows an effective
multi-tap transformer measurement using a scanner
and the Agilent 4263B LCR meter.
The 4263B LCR meter is a low price instrument which
measures the fundamental parameters of LCR components
with speeds as fast as 25ms, at frequencies of 100, 120,
1k, 10k and 100kHz, In addition, with option 001, the
4263B measures turns ratio (N), mutual inductance (M)
and dc resistance (DCR) which are required for
transformer measurement. Figure 1 shows a 4263B
simple block diagram for L, M, and DCR measurement.
For example, in the inductance-turns ratio (L-N)
measurement, an ac voltage is applied at the Hcur
terminal. Self-inductance value (L1) is calculated from
the measured values of V1 and I1. Turns ratio (N) is
automatically obtained from the ratio of measured values
V1 and V2 (discriminating the polarity simultaneously).
In the dc resistance (of L-DCR) measurement, the applied
voltage at the Hcur terminal is dc. Dc resistance value
(DCR1) is calculated from the measured values V1 and I1.
There are, however, the following limitations when using
the measurement connection.
• Only primary self-inductance and dc resistance of
the transformer can be measured. For the secondary
values, the transformer connections must be changed.
• Turns ratio must be 0.9 or more (In the case of less
than 0.9, the measurement is not performed due to
saturation of internal circuitry).
Agilent 16060A transformer test fixture can be used
to overcome these limitations. By changing the external
switch of this fixture, connections to the transformer
are changed and thus both primary and secondary
parameters and turns ratio can easily be measured.
Figure 2 shows the simple block diagram of the 16060A.
Figure 1. Agilent 4263B block diagram for L, M, and DCR measurement
Figure 2. Agilent 16060A block diagram
2
935955107.016.png 935955107.017.png 935955107.018.png
Multi-Tap Transformer Measurement
Using a Scanner
Multi-tap transformers having two or more poles can be
measured with the 4263B and a scanner.
(B) System construction recommendations
When constructing the system, the following points must
be considered to assure the measurements are as precise
as can be. (See figure 5)
(A) System configuration
Figure 3 shows the system configuration for measuring a
multi-tap transformer that has 4 taps.
1.Make measurement cables as short as possible. The
parasitic inductance and resistance of measurement
cables make a large contribution to measurement
error. For recommendable length, conductive wire
inductance value must be 1/10 or less than the
measured inductance value (similarly conductive
wire resistance).
The Agilent 3488A switch/control unit with a 4 x 4
matrix switch module (Opt. 013) is used. Option 013
offers highly flexible switching, and any combination of
4 input channels may be connected to any combination
of 4 output channels. Thus option 013 is suitable for
testing the multi-tap transformer. Figure 4 shows the
hardware configuration of the 4 x 4 matrix switch
module.
2.Configure into a shielded 2 terminal configuration,
to prevent the influence of external noise or stray
capacitance.
3.Connect the low terminals close to the transformer.
In the 4263B transformer measurement, the primary
and secondary inductors’ low terminals of the
transformer must be connected together. When
using a scanner, these connections should be close to
the transformer under test. If connecting at a far point
from the transformer (for example, input point of
scanner module), low side wire resistance would
contribute to increase measurement error.
Figure 3. System configuration for multi-tap transformer
Figure 4. Option 013 4 x 4 matrix module
Figure 5. System construction
3
935955107.019.png
(C) Measurement procedure
All measurements of the multi-tap transformer,
self-inductance, dc resistance, and turns ratio, can be
measured with only one connection by using the sample
program shown at the end of this note ( for HP 9000
Series 300 Controller). Figure 6 show the flow chart of
the sample program.
Figure 6. Flow chart of sample program
4
935955107.020.png
This program executes the open and short corrections
and displays each measured value of each tap of the
transformer. If turns ratio measurement cannot be made
due to the condition that turns ratio must be 0.9 or
greater, the scanner will be automatically changed and
the measurements re-done. This program can be modified
to match other systems or conditions.
The following steps outline the program procedure:
Step 1. Run the program. The following message is
displayed on the controller’s display.
Selection (1) Measurement (2) Correction ?
Type number and press RETURN key
Figure 7. OPEN Condition
At this point, select the measurement directly , or first
the measurement of correction data. To execute the
measurement, type 1 and press RETURN key on the
controller (Go to step 4). To measure the correction data,
type 2 and press RETURN key on the controller.
Step 2. If the measurement of correction data in step 1
was selected, the following message is displayed
on the controller’s display. The open correction
data of each channel of the scanner (CH.0-CH.3)
is now measured.
CH.0 Open measurement
Open test terminals of CH.0
Start open meas. (2) Skip CH.0 open meas?
Type number and press RETURN key
To measure the open correction data, set all channels
to the open condition as shown in figure 7. Then, type 1
and press RETURN key on the controller. Open correction
data of channel number 0 (CH.0) is acquired. Continue
to acquire data for channels 1 - 3.
5
935955107.021.png 935955107.022.png 935955107.023.png
Zgłoś jeśli naruszono regulamin