gmm_instrukcja-obslugi_metriso-500D_gb.txt

(41 KB) Pobierz
Operating Instructions 

Operating Instructions 
METRISO500D 


3-348-626-02 

Insulation Tester 4/12.05 



(2) 
(3) 
(7) 
(4) (5) (6) (7) (9) (8) (10) (11) 
GOSSEN METRAWATT GMBH 


(14) 
(12) 
(14) 
(12) 
Pushbutton for CONTINUOUSLY ON 
(2) Pushbutton 
 
for switching to autoranging with ISO-. measurement, 
(13) 
 
for measuring with automatic polarity reversal 
with . measurement and 
 
for switching the lamp in the probe on 
(3) Pushbutton 
 
for manual switching to higher measuring ranges 
with ISO-. measurement and 
 
for . measurement with current direction from + to  
(4) Pushbutton 
 
for manual switching to lower measuring ranges 
with ISO-. measurement and 
 
for . measurement with current direction from  to + 
(5) LCD display 
(6) Rotary switch for function selection 
(7) Supports for fastering of the carrying strap 
(8) Measurement pushbutton 
(9) Fixed probe with lamp (negative pole) 
(10) Fixed probe (positive pole) 
(11) Crocodile clips for attachment to probes (Z110J) 
(12) Holder for probe with lamp (9) 
(13) Probe holder (10) 
(14) Carrying strap 
GOSSEN METRAWATT GMBH 


Contents 

Contents 
5 
2 Applications ..........................................................6 
3 Getting started ......................................................6 


3.1 
Inserting the batteries .............................................6 
3.2 
Testing the batteries ...............................................6 
3.3 
Fastening the carrying strap and the probe holders ...7 
3.4 
Switching the tester on and off ................................ 8 
4 LCD display ...........................................................8 
5 Detecting dangerous touch potentials .................9 
6 Measuring DC and AC voltages ............................9 
7 Measuring the insulation resistance ..................10 


7.1 
ISO-. measurement with autoranging ...................10 
7.2 
ISO-. measurement with manual range selection ..13 
7.3 
Evaluation of the measured values .........................15 
8 
Measuring low-ohmic resistances (O . . . 30 .) 16 

8.1 
Measuring with automatic polarity reversal .............16 
8.2 
Measuring with manual polarity reversal .................17 
8.3 
Determining the maximum display values with 
allowances made for maximum service error .........19 
9 Specifications ....................................................20 
10 Maintenance .......................................................24 


10.1 Messages on the LCD display ................................24 
10.2 Testing the LCD display .........................................24 
10.3 Batteries ..............................................................24 
10.4 Fuse ....................................................................25 
10.5 
Lamp in the probe ................................................25 
10.6 
Case ....................................................................25 
11 
Repair and Replacement Parts Service 

DKD Calibration Lab 

and Rental Instrument Service ...........................26 


12 
Product Support .................................................27 



GOSSEN METRAWATT GMBH 


1 Safety precautions 

1 Safety precautions 

To maintain the safe and proper condition of the tester and to 
ensure its safe operation, it is absolutely necessary to carefuily 
and completely read these operating instructions before using the 
tester. These instructions must be followed in all respects. 

Repair and replacement of parts 

When opening the tester, live parts may be exposed. The 
tester must be disconnected from all voltage sources prior 
to repair or replacement of parts. If a repair cannot be 
avoided unless the tester is open and live, this must be performed 
by a qualified person who understands the danger 
involved. 

Faults and extraordinary stress 

When it must be assumed that safe operation is no longer 
possible, take the meter out of service and secure it against 
accidental use. It is assumed that safe operation is no 
longer possible, 

 when the tester shows obvious signs of damage, 
 when the tester no longer functions correctly, 
 after prolonged storage under adverse conditions. 
!
Attention! 

The fixed test leads have a double insulation in different 
colors. You can readily recognize damaged 
leads by the light insulation on the inside. 

Meaning of the symbols on the device 

!
Warning of a danger point 
(Attention, refer to documentation) 
Double or reinforced all-insulation 


Mark approval by testing board 


EU-Conformity Mark 

This device may not be disposed of with the trash. 
Further information regarding the WEEE mark can 
be accessed on the Internet at www.gossenmetrawatt.
com under the search term WEEE. 


GOSSEN METRAWATT GMBH 


Applications 

Applications 
/ 
EN 61557 / VDE 0413 Measuring and monitoring facilities 
for testing the electrical safety in lines with nominal voltages 
up to AC 1000 V and DC 1500 V. 
Part 1 General; 
Part 2 Insulation resistance; 
Part 4 Resistance measuring devices. 


It is suited to measure the insulation resistance of electrically 
dead devices and systems having nominal voltages up to 
500 V and to test the resistance of ground conductors, protective 
conductors and equipotential conductors including 
their connections and connectors. 


In addition, the tester has a 500 V measuring range for DC 
and AC voltage which complies with DIN VDE 0100 
Part 610. This makes it particularly advantageous to test 
devices for the absence of voltage and to discharge capacitive 
devices under test. 
The most important applications of the insulation tester are 
found in testing of systems and appliances such as required 
by DIN VDE 0100, 0105, 0141, 0701 and 0702 specifications, 
for example. 


3 Getting started 

3.1 Inserting the batteries 
!
Attention! 

Make sure that the rotary switch (6) is set to the 
OFF position prior to opening the battery compartment 
and that the tester is completely disconnected 
from all external circuits! 

1 
Undo the two slotted screws on the bottom ot the tester 
with an adequate tool and remove the cover of the battery 
compartment. 

1 
Insert 6 each 1.5V mono-cells to IEC R20 (zinc-carbon) 
or to IEC LR20 (alkaline-maganese) in the battery compartment. 
paying attention to the correct polarity in line 
with the given symbols. 

1 
Replace the cover of the battery compartment and 
tighten the screws. 

3.2 Testing the batteries 
1 
Set the rotary switch (6) to position -II-. 
The charging state of the six mono-cells is tested at this 
position. To simulate operating conditions, the lamp in the 
probe is switched on. 

The digital display shows the battery voltage at this load on 
the LCD display (5). 


GOSSEN METRAWATT GMBH 


At the same time, the analog indicator shows the nominal 
range of use of the battery voltage. You can quickly judge 
the charging state of the battery set by the location of the 
pointer. 

At the same time, the analog indicator shows the nominal 
range of use of the battery voltage. You can quickly judge 
the charging state of the battery set by the location of the 
pointer. 


The battery test is automatically stopped after about 
10 seconds. The lamp goes out and HOLD is shown on 
the LCD dieplay (5) in addition to the digital display and the 
analog indication. This presentation is maintained until the 
tester automatically switches back to standby after 
approximately 3 minutes. until you press the measurement 
pushbutton (8) or until you set the rotary switch (6) to 
another position. 

You start a new battery test by pressing the measurement 
pushbutton (8). 

3.3 Fastening the carrying strap and the probe holders 
Probe holder 
Carrying strap 
Catch 
Metriso 500D 
Fasten the carrying strap 

(14) and the two probe 
holders (12) and (13) as 
shown in the following figure. 
Make sure to fix the 
holder for the slim probe 
(10) at the left and the 
holder for the probe with 
lamp and pushbutton (9) 
at the right. 
GOSSEN METRAWATT GMBH 


3.4 3.4 
1 
Set the rotary switch (6) from the OFF position to position 
500 V 


, ISO-. or .. 
When set to the 500 V  position, the measuring range for 
DC and AC voltage is switched on. Digital display and analog 
indication are presented. 

When set to the lSO-. position, the tester is switched to 
standby. The digital display only shows the decimal point 
together with the numeral 3 and the unit M., and the analog 
indicator shows the measuring range 500 V. 

When set to the . position, the tester is switched to 
standby. The digital display only shows the decimal point 
together with the number 30 and the unit .. 
After measuring at the . and ISO-. positions, the tester 
automatically switches to standby, 

 
when the rotary switch is not operated for approximately 
3 minutes and when no other pushbutton is pressed 
 
when the measured value does not change for approximately 
3 minutes 
 
when no voltage above 25 V is applied to the probes for 
more than 3 minutes on the 500 V 
 range. 
1 
To reactivate the tester, press any pushbutton on the 
tester or the pushbutton (8) in the probe, or set the 
switch (6) to another position. 

CONTINUOUSLY ON 

When set to the ISO-. and . positions, the tester measures 
only as long as you keep the pushbutton (8) in the 
probe pressed (an exception is the AUTO function at position 
., see section 8.1). 
When set to these positions, you also can switch the tester 
CONTINUOUSLY ON: 
1 
Briefly press the measurement pushbutton  


 (1) on the 
tester. 
You can cancel CO...