APC Smart 750 1000 1500 RACK.pdf
(
1608 KB
)
Pobierz
UserÓs Manual
English
§
Smart
-UPS
UPS
750VA/1000VA/1500VA
100/120/230VAC
2U Rack Mount
Uninterruptible Power Supply
990-1194 5/02
Introduction
The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags,
and surges from reaching your computer and other valuable electronic equipment. The UPS filters
small utility line fluctuations and isolates your equipment from large disturbances by internally dis-
connecting from the utility line. The UPS provides continuous power from its internal battery until
the utility line returns to safe levels or the battery is discharged.
1: I
NSTALLATION
Read the Safety Instruction sheet before installing the UPS.
Unpacking
Inspect the UPS upon receipt. APC designed robust packaging for your product. However, accidents
and damage may occur during shipment. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the UPS, the front bezel, the rail kit, and a litera-
ture kit containing:
Product documentation and safety information
•
CD-ROM with additional user manual language support and safety information
•
PowerChute
§
CD-ROM
(120V/230V models only)
•
Serial and USB communication cables
•
Two IEC jumper cables and one plug adaptor
(230V models only)
•
The UPS is shipped with the battery disconnected.
Rail Installation
Install the rails following instructions in the rail kit.
Mounting rails are supplied for the standard 4-post rack. Two-post racks require only the mounting
brackets.
Ear Mounting Locations:
1. Standard
2.
2
Optional (1.4" setback)
3.
2-post rack (5" setback)
3
1
1
Positioning the UPS
Place the UPS where it will be used.
The UPS is heavy. Select a location sturdy enough to handle
the weight.
Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the
specified limits.
0»- 40»C (32»-104»F)
0-95% Relative Humidity
P
LACEMENT
2.5 cm (1 in.)
Mounting the UPS in a Rack
The UPS is heavy.
To lighten it, you may remove the battery before mounting the unit in the rack
(Steps 1 and 2).
Step 1
Step 2
Caution: The battery is heavy.
Step 3
Install the UPS at or near the bot-
tom of the rack (Step 3).
Check to ensure the rack will not
tip after installing the UPS into
the rack.
2
Installing and Connecting the Battery and Attaching the Front Bezel
Step 1
Step 2
Step 3
Step 4
Connect battery plug to UPS. Tuck white battery
cord into space above connector.
Connecting Equipment and Power to the UPS
S
MART
-UPS R
EAR
P
ANEL
100/120V Models
120V Model Only: Site wiring fault indicator
230V Models
3
Plik z chomika:
f.r.e.d
Inne pliki z tego folderu:
APCFIXAPCFIX 2.8.1.196.exe
(3750 KB)
APCFIX APCFIX.2..8.1.196.zip
(1730 KB)
APC SMART 450 700 1000 1400 2200 3000.pdf
(260 KB)
APC SMART 600 ups instrukcja.pdf
(304 KB)
APC SMART 600.pdf
(304 KB)
Inne foldery tego chomika:
Huawei
JVC
Kondensatory Audio
LG
NIKON
Zgłoś jeśli
naruszono regulamin